We have made some recent enhancements online; you may need to clear your cookies to download Datasheets or call +49 7181 483 900

Temperature Limiter Q

Temperature Limiter Q

Area of Application

The temperature limiter Q is used wherever, on the one hand, protection against overtemperatures is required, and, on the other hand, automatic cut-in of the device to be protected - subsequent to a follow-on cooling down period - is undesirable or not permissible.

Mounting brackets or clips available.

Function

The temperature limiter Q operates independent from any current supply. Temperature detection is effected by means of a bimetal disk which was first dimensioned in accordance with the required cut-off temperature. When this fixed cut-off temperature TA is reached, this bimetal disk will snap over, breaking a contact system and thereby interrupting the electric circuit of the device to be protected. In order to prevent any automatic cut-in of the circuit when the switch cools down again, the switch is equipped with an electric latch/self-holding device.
 

Self-holding Function

By means of a resistor heat is generated by the supply voltage applied after breaking the contact. This heat prevents any decrease in temperature below the value necessary for the cut-in temperature TE. In this way, the switch will keep its contact open, irrespective of its ambient temperature. To close the contacts of the switch, and thus closing the current circuit, will be possible only after disconnection from the power supply.

 

Datasheet Q
Self-hold Resistor table

Download File